| Electrical Details, Diagrams & Tables
TYPICAL ELECTRICAL SERVICE DETAIL


CONDUCTOR SIZE AND CONDUIT REQUIREMENTS
MAXIMUM ALLOWABLE CURRENT CARRYING CAPACITY IN AMPERES OF INSULATED CONDUCTORS IN CONDUITS OR CABLES (TW insulation and not more than three conductors in conduit or cables.)
Size AWG | Amperes (Copper) | Amperes (Aluminum) | No. 14 | 15 | - | No. 12 | 20 | 15 | No. 10 | 30 | 25 | No. 8 | 40 | 30 | No. 6 | 55 | 40 | No. 4 | 70 | 55 | No. 2 | 95 | 75 | No. 1 | 110 | 85 | No. 0 | 125 | 100 |
Note: When installing more than three conductors in conduit or cables, see Note 8, Table 310-16 for derating factors (National Electrical Code).
MAXIMUM NUMBER OF TW CONDUCTORS IN CONDUIT OR TUBING
Size AWG | Conduit or Tubing Size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | No. 14 | 9 | 15 | 25 | 44 | 60 | 99 | No. 12 | 7 | 12 | 19 | 35 | 47 | 78 | No. 10 | 5 | 9 | 15 | 26 | 36 | 60 | No. 8 | 2 | 4 | 7 | 12 | 17 | 33 | No. 6 | 1 | 2 | 4 | 7 | 10 | 16 | No. 4 | 1 | 1 | 3 | 5 | 7 | 12 | No. 2 | 1 | 1 | 2 | 4 | 5 | 9 | No. 1 | - | 1 | 1 | 3 | 4 | 6 | No. 0 | - | 1 | 1 | 2 | 3 | 5 |
TYPICAL KITCHEN APPLIANCE BRANCH CIRCUITS
Receptacle outlets are required at each counter space wider than 12 in. spaced so that no point along the wall line is more than 24 in. from a receptacle. Island and peninsular type counter tops are required to have one receptacle for each 4 feet of counter-top. Counter-top outlets are required to be Ground Fault Circuit Interrupted (GFCI) protected. Outlets in the kitchen are required to be divided between two 20 amp. circuits. Primary task lighting in the kitchen must be fluorescent, however; secondary task lighting may be incandescent.

Type of Appliance | Branch Circuit Rating | Electrical range (240V) | 50 amperes | Kitchen counter top small appliance branch circuit (120V) | 20 amperes | Counter-mounted electric cooking unit (240V) | 30 amperes | |
|